Does lowering voltage increase current?

There are two facets to this question.

First, on a distribution feeder, lowering the voltage a few percent with AdaptiVolt™ does not, in most cases, increase current. It really depends on the load. For incandescent lighting (or other devices that follow the I*I*R rule), a drop in voltage reduces the current. For fluorescent lighting, a 1% drop in voltage results in a 1% drop in load, so the current stays about the same. For devices on a thermostat (i.e. ovens, residential heating, etc.), the energy demand would go down based on I*I*R, but the time "on" would increase proportionately to maintain the temperature set by the thermostat. If a significant motor load exists, the current for the motor may increase based on the characteristics of the motor. In any case, the AdaptiVolt™ system will track the load and adjust voltage up or down to minimize energy flow. For most commercial and residential feeders, we do not see an increase in current with the drop in voltage although we do see a drop in energy usage.

The second concern has to do with distribution feeder voltage. A 4 kV circuit will draw more current than a 12 kV circuit for the same load. In this case, the two feeders will be designed with different transformers, and because the voltage is three times greater in one case, the current will be one third for the same load. Under AdaptiVolt™, we use whatever distribution voltage a utility has. We use the same transformers, etc. We lower the voltage a small amount (typically less than 5%) and the resultant energy usage drops per the discussion above.

Return to FAQs

 

What is the best voltage for the customer?

The best voltage for the customer is the lowest voltage at which all electrical equipment, appliances and devices operate correctly and efficiently, offers the lowest operating cost and provides the longest life. This voltage is usually obtained when the service voltage is at the lowest ANSI C 84.1or CAN-3-C235-83 allowable voltage. We recommend that end-of-line voltages be controlled as close to Vac (Minimum Allowable Service Voltage + Estimated Transformer Voltage Drop) to hold service voltages to a minimum. ANSI minimum is 114. Vac and CAN minimum is 110 Vac for single-phase systems and 112 Vac for three phase systems. (Note for the purposes of this discussion all voltages are on a 120 volt base.)

Most motors are nameplate rated at voltages below the nominal system voltage. For example most motors designed to run on a nominal 120 Vac are actually rated to operate at 115 Vac. Furthermore, the motor manufacturers design their motors to operate within a range of voltages usually 5% below to 5% above the nameplate rating.

Tests for different motor applications have shown the following:

  • For freezer applications, average kWh per day drops when voltage is reduced. This indicates that there is an efficiency increase in kWh per degree setting because the freezer process is essentially a closed loop cooling process.

  • Central AC units become more efficient as voltage is reduced until voltage reaches almost 8% below the compressor motor nameplate rating.

  • Pool Pump tests in California show reduced kW and increased PF for voltages down to approximately 8% below nameplate.

Additionally:

  • Most new electronic ballast fluorescent and HID lighting become more efficient as voltage is reduced to as much as 7% below nominal voltage.

  • Incandescent lamp life and other heating element life increases with lower voltages.

  • When operating at the lower voltages there is no noticeable drop in overall lighting levels.

Return to FAQs

 

How does AdaptiVolt™ prevent customers' voltages from dropping below 114 volts?

AdaptiVolt™ continously measures end-of-line voltage and uses that measure as a basis for setting substation voltages.

Return to FAQs

 

 

Contact Us

Site Map

This site was last updated on 08/09/2007.

Copyright © 2006 PCS UtiliData.  All rights reserved.